TAMINI LF Transformer
12 MVA Ladle Furnace Transformer
Technical Details
Manufacturer: V.T.D. Trasformatori (Tamini Group), Italy
Year of Manufacture: 2006 (Serial No. 21399)
Type / Scope: Three-phase oil-immersed ladle furnace transformer, booster type (constant flux), with on-load tap changer, per IEC 76 / IEC 354
Key technical data:
- Rated power: 12 MVA
- Cooling type: OFWF (oil-forced, water-forced); installation: indoor
- Rated frequency: 50 Hz
- Primary voltage: 20 kV; secondary voltage: 180–280 V (11 tap positions, 10 V steps)
- Primary current: 346.41 A (pos. 7–11) down to 259.81 A (pos. 1); secondary current: 24,744 A (pos. 11) up to 28,868 A (pos. 1–7)
- Insulation level: primary 24–50–125 kV; secondary 1.1–8 kV
- Vector group: Dd (primary delta / secondary open delta)
- Short-circuit impedance: 6.88% / 9.48% / 13.89% (pos. 11 / 7 / 1, referred to 12 MVA)
- Rated ratio: 20/0.28, 20/0.24, 20/0.18 kV
- Temperature rise (35°C cooling water inlet): at 12 MVA, two coolers in operation: winding 55K, oil 50K
- On-load tap changer: 11 positions; constant power (12 MVA) on pos. 7–11, constant secondary current (28,868 A) on pos. 1–7; insulation class 24 kV
- Duty cycle: 100% continuous
- Current transformers CT1–CT3: 188.3/2.887 A, 100 VA, class 0.5 (corresponding to 30,000/√3 : 5/√3 A after delta closure)
- Total weight: 35,000 kg; oil weight: 9,000 kg; removable core & coil weight: 17,000 kg; tank designed for lifting when fully filled with oil
- Oil type: Transag 10 GBN
- Cooling water: 32,500 l/h per cooler (each cooler sized for 50% of losses); cooling capacity 150 kW per cooler; water pressure drop 0.3 bar; water inlet temperature 35°C
Tap changer positions (at 55K winding temperature rise):
- Pos. 11: 280 V – 24,744 A secondary – 346.41 A primary
- Pos. 10: 270 V – 25,660 A – 346.41 A
- Pos. 9: 260 V – 26,647 A – 346.41 A
- Pos. 8: 250 V – 27,713 A – 346.41 A
- Pos. 7: 240 V – 28,868 A – 346.41 A
- Pos. 6: 230 V – 28,868 A – 331.98 A
- Pos. 5: 220 V – 28,868 A – 317.55 A
- Pos. 4: 210 V – 28,868 A – 303.11 A
- Pos. 3: 200 V – 28,868 A – 288.68 A
- Pos. 2: 190 V – 28,868 A – 274.25 A
- Pos. 1: 180 V – 28,868 A – 259.81 A
Oil-water heat exchanger (per cooler):
- Manufacturer: Boldrocchi, Biassono (Milan), Italy
- Construction No.: EQ 76170/01
- Power exchanged: 150 kW
- Water flow rate: 32.5 m³/h; oil flow rate: 22 m³/h
- Max water temperature: 35°C
- Temperature difference: water 4K; oil 15K
- Weight: 490 kg without oil; oil content approx. 150 kg
Project Value
End-to-end project management covering acquisition, disassembly, logistics, and compliance — executed with precision and global fluency.

More Machines from The Same Product Line
Explore additional assets from the same automotive painting and assembly line—available for standalone purchase or full-line relocation.
Machinery from The Same Factory
Explore high-value equipment originally operated within this factory—available individually or as part of a larger line or plant acquisition.
Your Contacts for This Project
Have questions about the machine, logistics, or technical details? Reach out directly to our specialists—they’ll guide you through every step with clarity and care.